Fire curtains EI 30, EI 60, EI 90, EI120 (without irrigation)
Why you should work with us:
- We are direct manufacturers of fire barriers under the brands MBA and FireTechnics (confirmed by certificates);
- The products are tested and certified according to the Federal Law of the Russian Federation, read more;
- The fabric is of European quality, purchased in Germany and meets the requirements of Federal Law No. 123 (from 2020 to TR NPP), unlike Chinese analogues;
- Production, design, delivery, installation, maintenance - turnkey fire curtains;
- License of the Ministry of Emergency Situations and SRO;
- Warranty and service.
Completed works
The design and principle of operation of the fire curtain
There are two types of fire curtain designs, depending on the drive used:
-
The Gravigen system is a system that allows you to block the opening even in the absence of electricity. The curtain is held by an electromagnet and when a signal is received from the remote control about a fire, the contact opens and the curtain falls under the influence of gravity. A natural question arises, but what happens if there is no fire, and the electricity in the building is turned off? In this case, the magnet is powered by an uninterruptible power supply and remains operational for up to 72 hours.
-
The system with an intravenous motor - the system works to open and close the opening from electricity and is controlled from the remote control of the fire protection system, when the power is turned off, the curtain can be lowered due to the battery. Please note that most of the curtain drives are powered by a 220 volt mains.
Types of fire curtains
Depending on the composition of the canvas, non-flammable curtains without irrigation can be of different fire resistance: from EI15, EI30, EI45 to EI60, EI90, EI120. For the EI 60 with irrigation, a single-layer construction with a heat-resistant fabric and a cut-off tire at the bottom is used. To increase fire resistance, a multilayer structure is used, where the inner layer contains a bulging carbon layer that expands when heated. The EI value shows how many minutes the barrier will withstand a fire.
E - loss of integrity;
I is an indicator of thermal insulation ability.
In 2021, we received new EAEU certificates for fire curtains with a fire resistance of 60 and 120 minutes, which means we can supply fire-resistant curtains for buildings with projected barriers from 15 to 120 minutes inclusive.
Integration of fire protection with fire alarm systems
Our fire barriers perfectly integrate with all fire systems and alarms of both Russian and foreign production. It is enough to output a control signal (dry contact) to our control unit from the fire alarm system. Fire barriers can be closed automatically when the alarm is triggered and controlled manually, if necessary.
The box of the fire-retaining screen
It consists of three bent, galvanized sheet steel 1.5 mm panels, up to 3 m long. To build long curtains, the panels are docked with each other. Both ends of the case are closed with covers that hermetically close the circuit. The side covers also serve to sense the torque of the tubular motor. The overall dimensions of the box depend on the height of the blocked opening.
Color version: any color on the RAL color scale or galvanized steel.
Maximum dimensions of fire-resistant curtains
Width, max., mm: | 12 000 | |
Height, max., mm: | 12 000 | |
Box (depth × height): at a height of less than | 4 m 200 × 220 mm | at a height of more than 4 m 300 × 330 mm |
We will be able to produce products according to individual sizes, check with the manager.
The installation of fire barriers is regulated by Federal Law No. 123 and such systems are not installed without an approved project. In some cases, at the request of the fire inspection, fire curtains are installed in those buildings that were designed according to old standards and do not meet modern fire safety requirements.
Fire curtains are used in the construction of parking lots, entertainment and shopping centers, cinemas, theaters, museums and other facilities for various purposes. Fire-resistant curtains are also installed during the construction of warehouses, industrial premises, administrative, medical and educational institutions.
Most often we install fire/smoke-proof curtains on atriums, checkout areas, elevator openings, vestibule locks, entrance and window openings, but there are other openings provided for by the project, for example, horizontal openings, conveyor openings and large concert halls. Examples of the use of fire-resistant MBA curtains on real objects can be found in the section COMPLETED WORKS
Main advantages:
-
reinforced European fabric with good strength and fire resistance indicators;
-
a design developed over years and experience, originally created by Stöbich engineers;
-
license and compliance with FZ 123;
- a control unit of its own production and integration with fire protection systems and remote controls.
The price of fire curtains is formed individually and depends on many factors, such as the type of drive used, the color of the guides and the box, the size of the structure, the degree of fire resistance. Plus, the price can include delivery and installation of curtains on a turnkey basis. The website shows the minimum approximate price per square meter.